Hydrovar X configuration for Xylem Vue Secure Connect

På Hydrovar X-enheden skal der trykkes på op- og ned-tasten for at ændre undermenuerne.

  1. Gå til kommunikationsindstillingerne på M08.
  2. Indstil følgende parametre.
Id Parameter Indstilling
P08.0.02 Kom 2-funktion 1-Modbus
P08.1.01 Adresse 1-127
P08.1.02 Baudrate 115200 bps
P08.1.08 RTU-format 8, N,1
Format = 8 bit
Paritet = Ingen
Stopbits = 1