FPG 411 / FPG 412 Configuration

  1. Press the Home button.
  2. Go to  and press to select all the menus.
  3. Go to Settings > Communication.
  4. Select RS-485 RTU Port or Ethernet Port.
  5. Set the communication parameters.
  • RS-485 RTU Port
Parameter Setting
Protocol settings Modbus Slave
Slave address The controller address in the network
Channel settings Baud - 9600
Parity - None

 

  • Ethernet Port
Parameter Setting
Protocol Modbus Slave
Channel settings IP address - 10.10.10.10
Subnet mask - 255.0.0.0
Port - 502