Hydrovar X configuration

On the Hydrovar X device, the up and down key must be pressed to change the submenus.

  1. Go to the communication settings at M08.
  2. Set the following parameters.
ID Parameter Setting
P08.0.02 Com 2 Function 1-Modbus
P08.1.01 Address 1-127
P08.1.02 Baudrate 115200 bps
P08.1.08 RTU Format 8, N,1
Format = 8 bits
Parity = None
Stop bits = 1