Parece que você está vindo de United States, mas o site atual que você selecionou para visitar é Brazil. Você quer mudar de site?

Sim, por favor. No. Keep me on the current site.

Enable high contrast mode

PS 220 Configuration

The user can choose between TCP or RTU Modbus communication

Modbus TCP

The FMBT-21 device must be installed in slot 2.

Set the following parameters.

Parameter Parameter name Setting
50.1 FBA A ENABLE [2] Option slot 2
74.01 START/STOP [6] Fieldbus
74.05 SPEED OVERRIDE [6] Fieldbus
74.06 SPD OVERRIDE [3] Fieldbus
51.01 FBA A type [128] Ethernet
51.02 Protocol/Profile [1] MB/TCP ABB E
51.03 Commrate [0] Auto
51.04 IP configuration [0] Static IP
51.05 IP address 1 10
51.06 IP address 2 10
51.07 IP address 3 10
51.08 IP address 4 20
51.09 Subnet CIDR 24
51.22 Word order 1 = HILO
51.23 Address mode [1] Mode 1
51.27 FBA A par refresh [1] Refresh

 

Modbus RTU

The FSCA-module must be installed in slot 2.

Set the following parameters.

50.1 FBA A ENABLE [2] Option slot 2
74.01 START/STOP [6] Fieldbus
74.05 SPEED OVERRIDE [6] Fieldbus
74.06 SPD OVERRIDE REF [3] Fieldbus
51.01 FBA A type [485] FSCA
51.02 Protocol/Profile [1] MB/TCP ABB E
51.03 Station ID 1
51.04 Baud 9600
51.05 Parity None
51.25 Protocol [1] Modbus
51.27 FBA A par refresh [1] Refresh