XAM 912 Configuration
Enable the Modbus RTU or TCP protocol in the Setup Wizard to allow communication.
RS-485 RTU port
- Go to Settings > Communication > Modbus > Modbus server.
- Set the communication parameters.
| Parameter | Setting | 
| Server ID | 1 | 
| Baud | 19200 | 
| Stop bits | 1 | 
| Parity | Even | 
| LED off delay | 60 s | 
Ethernet
- Go to Settings > Communication > Modbus > Modbus server > TCP/IP.
- Set the communication parameters.
| Parameter | Setting | 
| IPv4 address | Use the IP address set on TCP/IP. For the XAM 912 port, the default value is 10.10.20.10 | 
| Port | Default value: 502 The user can choose a value between 500-65535 |