SENECA Z-D-IN/Z-10-D-IN Configuration
The module must be turned off before it is configured. Configure the communication settings by using the DIP switch.
- Set the baud
| DIP Switch position 1 | DIP Switch position 2 | Baud | 
| - | - | 9600 | 
| - | On | 19200 | 
| On | - | 38400 | 
| On | On | 57600 | 
| - | - | EEPROM | 
- Set the address.
| DIP Switch position 3 | DIP Switch position 4 | DIP Switch position 5 | DIP Switch position 6 | DIP Switch position 7 | DIP Switch position 8 | Address | 
| - | - | - | - | - | On | 1 | 
| - | - | - | - | On | - | 2 | 
| - | - | - | - | On | On | 3 | 
| - | - | - | On | - | - | 4 | 
| - | - | - | - | - | - | --- | 
| On | On | On | On | On | On | 63 | 
| - | - | - | - | - | - | EEPROM | 
- Set the status of the RS-485 terminator.
| DIP Switch position 10 | Status | 
| -- | Disabled | 
| On | Enabled |