PS 220 Configuration

The user can choose between TCP or RTU Modbus communication

Modbus TCP

The FMBT-21 device must be installed in slot 2.

Set the following parameters.

Parameter Parameter name Setting
50.1 FBA A ENABLE [2] Option slot 2
74.01 START/STOP [6] Fieldbus
74.05 SPEED OVERRIDE [6] Fieldbus
74.06 SPD OVERRIDE [3] Fieldbus
51.01 FBA A type [128] Ethernet
51.02 Protocol/Profile [1] MB/TCP ABB E
51.03 Commrate [0] Auto
51.04 IP configuration [0] Static IP
51.05 IP address 1 10
51.06 IP address 2 10
51.07 IP address 3 10
51.08 IP address 4 20
51.09 Subnet CIDR 24
51.22 Word order 1 = HILO
51.23 Address mode [1] Mode 1
51.27 FBA A par refresh [1] Refresh

 

Modbus RTU

The FSCA-module must be installed in slot 2.

Set the following parameters.

50.1 FBA A ENABLE [2] Option slot 2
74.01 START/STOP [6] Fieldbus
74.05 SPEED OVERRIDE [6] Fieldbus
74.06 SPD OVERRIDE REF [3] Fieldbus
51.01 FBA A type [485] FSCA
51.02 Protocol/Profile [1] MB/TCP ABB E
51.03 Station ID 1
51.04 Baud 9600
51.05 Parity None
51.25 Protocol [1] Modbus
51.27 FBA A par refresh [1] Refresh