SENECA Z-8AI Configuration
The module must be turned off before it is configured.
- Configure the Modbus settings by using the SW1 DIP switch.
a) Set the baud.
DIP Switch position 1 | DIP Switch position 2 | Baud |
- | - | 9600 |
- | On | 19200 |
On | - | 38400 |
On | On | 57600 |
- | - | EEPROM |
b) Set the address
DIP Switch position 3 | DIP Switch position 4 | DIP Switch position 5 | DIP Switch position 6 | DIP Switch position 7 | DIP Switch position 8 | Address |
- | - | - | - | - | On | 1 |
- | - | - | - | On | - | 2 |
- | - | - | - | On | On | 3 |
- | - | - | On | - | - | 4 |
- | - | - | - | - | - | --- |
On | On | On | On | On | On | 63 |
- | - | - | - | - | - | EEPROM |
c) Set the status of the RS-485 terminator.
DIP Switch position 10 | Status |
-- | Disabled |
On | Enabled |
- Set all SW2 DIP switches to ON to set all input ports to measure current.
Avensor only supports the SENECA Z-8AI module when it is used as an input for a 4–20 mA current.
DIP Switch position 1-8 | Mode |
-- | Voltage |
On | Current |
-
To configure the channels update the following registers with a Modbus tool. Make sure that the tool aligns with your security and operational requirements.
Registers for electrical input
Range: ±10000 [mV] for voltage, ±20000 [µA] for current
Interpretation of register: Word
Input
Register
Input 1
40014
40015
Input 2
40020
40021
Input 3
40026
40027
Input 4
40032
40033
Input 5
40038
40039
Input 6
40044
40045
Input 7
40050
40051
Input 8
40056
40057
Registers for the value to show or scale
Range: ±32000
Interpretation of register: Word
Input
Register
Input 1
40016
40017
Input 2
40023
40024
Input 3
40028
40029
Input 4
40034
40035
Input 5
40040
40041
Input 6
40046
40047
Input 7
40052
40053
Input 8
40058
40059
For further details on register values and setup, refer to the device documentation.