General Information | 3000 |
---|---|
UV transmittance range in % (1cm) | 65 - 98 |
Maximum flow rate (m³/h / MGD) | 4100 / 18052 |
Validation type | UVDGM, DVGW |
UV Lamps and Monitoring System | 3000 |
---|---|
Lamp technology | Medium Pressure |
Power per lamp | 9000 |
Number of lamps per row | 5 |
Lamp life (hours) | 8000 |
Lamp certification | 3rd party on aging and UV-C output |
UV intensity monitoring | germicidal, ÖNORM compliant |
Control philosophy | OptiDose(true sensor based variable lamp output) |
Individual lamp monitoring | Yes |
UV Reactor | 3000 |
---|---|
UV reactor protection class | IP54 |
Cleaning system | automatic, mechanical |
Reactor material | Stainless steel 1.4404 / 1.4435 (ASTM 316L) |
Flange size | DN 600 / ANSI 24" |
Reactor length (m / in) approx. | 1200 / 47.3 |
Maximum operating pressure (bar/PSI) | 10 / 145 |
Operating temperature (C/F) | 5 – 30 °C (41 – 86°F) |
UV System Control Cabinet | 3000 |
---|---|
Ballast type | Electronic, high-efficiency, variable output (30 to 100% power) |
Controller | PLC |
UV system control cabinet material | Painted sheet steel or Stainless steel |
UV electrical standards | CE, UL, cUL |
Common outputs | System Status, Lamp Status, Alarm Messages, Process Values |
UV system control cabinet scada communication | Yes (option) |
Power consumption (kW) approx. | 48 |
Supply voltage (V / V / Hz) | CE/cUL: 400/480V +-10%; 50/60Hz. TN- net.L1,L2,L3, PE / WYE |
Protection class | IP 54 / cUL Type 12 |