SENECA Z-D-IN/Z-10-D-IN Configuration
The module must be turned off before it is configured. Configure the communication settings by using the DIP switch.
- Set the baud
DIP Switch position 1 | DIP Switch position 2 | Baud |
- | - | 9600 |
- | On | 19200 |
On | - | 38400 |
On | On | 57600 |
- | - | EEPROM |
- Set the address.
DIP Switch position 3 | DIP Switch position 4 | DIP Switch position 5 | DIP Switch position 6 | DIP Switch position 7 | DIP Switch position 8 | Address |
- | - | - | - | - | On | 1 |
- | - | - | - | On | - | 2 |
- | - | - | - | On | On | 3 |
- | - | - | On | - | - | 4 |
- | - | - | - | - | - | --- |
On | On | On | On | On | On | 63 |
- | - | - | - | - | - | EEPROM |
- Set the status of the RS-485 terminator.
DIP Switch position 10 | Status |
-- | Disabled |
On | Enabled |