Compatible Devices
Modbus connected devices must be of the same connection type, for example, a Flygt APP 411 cannot be connected to the same CCD 401 as a Flygt DCM 711. It is possible to add devices that are connected directly to the gateway. That is, analog input and digital input/output. For some device types, multiple devices of that type can be added.
Devices that are not on the list of compatible devices can be added as Custom Devices.
I/O Devices
The user can choose any analog sensor (4-20 mA) or any digital sensor and connect directly to the CCD 401. The I/O devices connect to the CCD 401 through the signal leads. This type of sensor is considered as a device in Avensor.
Device | Maximum number of connected devices per gateway |
Analog input | 2 |
Digital input | 4 |
Digital output | 2 |
Devices with other connectivity types
Device | Maximum number of devices for each station |
Xylem optimyze | 10 |
ATU | 1 |
Remote inspection kit | 1 |
Devices with a CCD gateway connection
Below is a list of devices with a CCD gateway connection listing their connection type and the maximum number of connected devices per gateway.
Note – It is possible to retrieve data from more than one device in a system even if the maximum number of connected devices is one:
- The Concertor XPC system includes one APP 411 and up to three FPG 414. When the APP 411 connects to the gateway, Avensor retrieves data from all devices in the system.
- The Adaptive mixer ADC system includes one APP 412 and up to seven FPG 415. When the APP 412 connects to the gateway, Avensor retrieves data from all devices in the system.
Device | Connection | Maximum number of connected devices per gateway | Supported units |
Evoqua ATG UV | RS-485 or Ethernet | RS-485: 8 Ethernet - Flygt CCD 401: 4 |
Metric |
Evoqua DEPOLOX Pool Compact | Ethernet | 4 | Metric |
Flygt APP 411 | RS-485 or Ethernet | 1 Supports up to 4 pumps |
Metric, USCS and Imperial |
Flygt APP 412 | RS-485 or Ethernet | 1 Supports up to 8 machines |
Metric |
Flygt APP 521 Flygt APP 541 |
RS-232 | 1 | Metric |
Flygt DCM 711 | RS-485 or Ethernet | 1 | Metric |
Flygt FGC 313/323 | RS-232 | 1 | Metric |
Flygt FGC 401/411/421 | RS-232 or RS-485 | 1 | Metric |
Flygt FPG 411/412 Flygt FPG 413/414/415 |
RS-485 or Ethernet | RS-485: 8 Ethernet: 4 |
Metric |
Flygt Magflux | RS-485 | 8 | Metric |
Flygt MAS 711 | RS-485 | 8 | Metric |
Flygt MAS 801 | RS-485 | 4 | Metric, USCS and Imperial |
Flygt MyConnect | RS-232 or RS-485 | 1 Supports up to 2 pumps |
Metric |
Flygt SmartRun gateway | RS-232 or RS-485 | 1 Supports up to 3 pumps. |
Metric |
Flygt SRC 311 | RS-485 | 8 | Metric, USCS and Imperial |
Flygt PS 200 | RS-485 or Ethernet | Metric | |
Flygt PS 220 | RS-485 or Ethernet | RS-485: 8 Ethernet: 4 |
Metric |
Godwin PV102P | RS-485 | 8 | Metric |
Lowara EPX Plus Mobile Heater | RS-485 | 1 | Metric |
Lowara Hydrovar HVL | RS-485 | 8 | Metric |
Lowara Hydrovar X | RS-485 | 4 | Metric |
PSMEGA 2 | RS-485 | 1 | Metric |
Sanitaire Digital Pressure Monitor | Ethernet | 1 | Metric |
Sanitaire Taron | RS-485 or Ethernet | 1 | Metric |
Sanitaire TurboLIGHT | RS-485 or Ethernet | 1 | Metric |
Sanitaire TurboMAX Dual Core | RS-485 | 1 | Metric |
Sanitaire TurboMAX Single Core | RS-485 | 1 | Metric |
SENECA Z-8AI | RS-485 | 8 | Metric |
SENECA Z-D-IN SENECA Z-10-D-IN |
RS-485 | 8 | Metric |
Wedeco EcoTouch | RS-485 | 1 | Metric |
Xylem Aquavar IPC | RS-485 | 4 | Metric |
Xylem XAM 912 | RS-485 or Ethernet | 1 (Support for Nexicon system up to 4 pumps, 2 I/O modules and 1 probe module. Pump modules supported are Standard pump, Dirigo and VFD) |
Metric, USCS and Imperial |