SENECA Z-8AI Configuration

The module must be turned off before it is configured.

  1. Configure the Modbus settings by using the SW1 DIP switch.
    a) Set the baud.
DIP Switch position 1 DIP Switch position 2 Baud
- - 9600
- On 19200
On - 38400
On On 57600
- - EEPROM

 

b) Set the address

DIP Switch position 3 DIP Switch position 4 DIP Switch position 5 DIP Switch position 6 DIP Switch position 7 DIP Switch position 8 Address
- - - - - On 1
- - - - On - 2
- - - - On On 3
- - - On - - 4
- - - - - - ---
On On On On On On 63
- - - - - - EEPROM

 

c) Set the status of the RS-485 terminator.

DIP Switch position 10 Status
-- Disabled
On Enabled

 

  1. Set all SW2 DIP switches to ON to set all input ports to measure current.
    Avensor only supports the SENECA Z-8AI module when it is used as an input for a 4–20 mA current.
DIP Switch position 1-8 Mode
-- Voltage
On Current

 

  1. To configure the channels update the following registers with a Modbus tool. Make sure that the tool aligns with your security and operational requirements.

    Registers for electrical input

    Range: ±10000 [mV] for voltage, ±20000 [µA] for current

    Interpretation of register: Word

     

    Input

    Register

    Input 1

    40014

    40015

    Input 2

    40020

    40021

    Input 3

    40026

    40027

    Input 4

    40032

    40033

    Input 5

    40038

    40039

    Input 6

    40044

    40045

    Input 7

    40050

    40051

    Input 8

    40056

    40057

     

    Registers for the value to show or scale

    Range: ±32000

    Interpretation of register: Word

     

    Input

    Register

    Input 1

    40016

    40017

    Input 2

    40023

    40024

    Input 3

    40028

    40029

    Input 4

    40034

    40035

    Input 5

    40040

    40041

    Input 6

    40046

    40047

    Input 7

    40052

    40053

    Input 8

    40058

    40059

     

    For further details on register values and setup, refer to the device documentation.

    https://www.seneca.it/media/6849154/mi00259-3-en.pdf