The CCD 401

The CCD 401 is a wireless gateway (a cellular modem) that is used to collect data from pumping stations. It contains an embedded eSIM for the wireless data transfer. Once the power and antenna is connected, the CCD is ready to use. When the CCD starts, it establishes the connection with Avensor automatically. The user can register the CCD by adding it to the Avensor during the station setup. The user can insert their own 3FF micro-SIM card in the SIM card slot. The 3FF micro-SIM card overrides the embedded eSIM.

The CCD sends your device location and data to the Avensor cloud. The user can see the location in Avensor under Station > Settings > Location. The CCD requires regular software updates, and Avesnor notifies the user whenever an update is available.

Visit the Connectivity FAQs for specific answers such as "Does CCD 401 have an internal battery?" or to watch a video on "How do I install and configure CCD 401?"

For additional information, download the CCD 401 Installation, Operation and Maintenance Manual.

Installing the CCD

  • Before installing the CCD, record the serial number or take a picture of the serial number of the CCD. After installation, the serial number is not visible.
  • The CCD must not be installed over 2 m (6.56 ft) height from the ground.
  1. Attach the antenna.
  2. Install the CCD on a DIN rail.
  3. Follow device-specific instructions to connect a device to the CCD.

[In general, the connection process may include one or more of the following steps:

  • Connect the Modbus TCP to the RJ45
  • Connect the RS-232 cable from the pump controller to the terminals.
  • Connect the RS-485 cable from the pump drive to the terminals.]

For more information about the devices that connect with the CCD, visit Compatible Devices.

Terminals

Terminal Description
E01 Not used
E02 Not used
GND Signal ground
485 A RS-485, 120 ohm termination resistor, A
485 B RS-485, 120 ohm termination resistor, B
E06 Digital output 1
E07 Digital output 2
GND Signal ground
E09 Not used
E10 Not used
DI1 Digital input 1, Pull up input
DI2 Digital input 2, Pull up input
GND Signal ground
DI3 Digital Input 3, Pull up input
DI4 Digital Input 4, Pull up input

 

Terminal Unit terminal
232 RX RTU Tx
232 Tx RTU Rx
GND Ground (earth)

 

Terminal Unit terminal
485 A A
485 B B
GND Ground (earth)

Special Device Connection

WARNING: Electrical Hazard
Risk of electrical shock or burn. A certified electrician must supervise all electrical work.
Comply with all local codes and regulations.

The following devices need a special connection to the gateway.

  1. Cut one end of the VGA cable.
  2. Connect the cut end of the VGA cable to the gateway according to the information below:
CCD Terminal Connector pin
Tx 2
Rx 3
GND 5
CTS/RTS 7/8 connected together