SENECA Z-D-IN/Z-10-D-IN Configuration

The module must be turned off before it is configured. Configure the communication settings by using the DIP switch.

  1. Set the baud
DIP Switch position 1 DIP Switch position 2 Baud
- - 9600
- On 19200
On - 38400
On On 57600
- - EEPROM

 

  1. Set the address.
DIP Switch position 3 DIP Switch position 4 DIP Switch position 5 DIP Switch position 6 DIP Switch position 7 DIP Switch position 8 Address
- - - - - On 1
- - - - On - 2
- - - - On On 3
- - - On - - 4
- - - - - - ---
On On On On On On 63
- - - - - - EEPROM

 

  1. Set the status of the RS-485 terminator.
DIP Switch position 10 Status
-- Disabled
On Enabled