SENECA Z-8AI Configuration

The module must be turned off before it is configured.

  1. Configure the Modbus settings by using the SW1 DIP switch.
    a) Set the baud.
DIP Switch position 1 DIP Switch position 2 Baud
- - 9600
- On 19200
On - 38400
On On 57600
- - EEPROM

 

b) Set the address

DIP Switch position 3 DIP Switch position 4 DIP Switch position 5 DIP Switch position 6 DIP Switch position 7 DIP Switch position 8 Address
- - - - - On 1
- - - - On - 2
- - - - On On 3
- - - On - - 4
- - - - - - ---
On On On On On On 63
- - - - - - EEPROM

 

c) Set the status of the RS-485 terminator.

DIP Switch position 10 Status
-- Disabled
On Enabled

 

  1. Set all SW2 DIP switches to ON to set all input ports to measure current.
    Avensor only supports the SENECA Z-8AI module when it is used as an input for a 4–20 mA current.
DIP Switch position 1-8 Mode
-- Voltage
On Current

 

  1. Configure the inputs
    a. Download the Seneca Easy Setup tool from the SENECA home page.
    b. Install the Seneca Easy Setup tool on a computer.
    c. Connect the SENECA Z-8AI module to the computer through a USB cable.
    d. Use the Seneca Easy Setup tool to configure the inputs.
Parameter Setting
Start scale 4000 uA, converted to 4000
Stop scale 20 000 uA, converted to 20 000
Sampling speed 120 ms