MAS 801 Configuration
The unit is connected to this device through the following terminals:
CCD 401 | MAS 801 |
RS-485 A | Modbus A+ |
RS-485 B | Modbus B+ |
- Go to Settings
- In the Modbus RTU group, set the following parameters:
Parameter | Setting |
Enable | Enabled |
Baudrate | 19200 |
Parity | None |
Stop bits | 2 |
- Click Save.
Note:
- One MAS 801 device must be added in Avensor for each pump.
- The Modbus ID in Avensor must correspond to the Modbus ID in the MAS 801 device.
- The Modbus id mapping group in the MAS 801 device shows the Modbus ID of each pump.