SENECA Z-8AI Configuration
The module must be turned off before it is configured.
- Configure the Modbus settings by using the SW1 DIP switch.
 a) Set the baud.
| DIP Switch position 1 | DIP Switch position 2 | Baud | 
| - | - | 9600 | 
| - | On | 19200 | 
| On | - | 38400 | 
| On | On | 57600 | 
| - | - | EEPROM | 
b) Set the address
| DIP Switch position 3 | DIP Switch position 4 | DIP Switch position 5 | DIP Switch position 6 | DIP Switch position 7 | DIP Switch position 8 | Address | 
| - | - | - | - | - | On | 1 | 
| - | - | - | - | On | - | 2 | 
| - | - | - | - | On | On | 3 | 
| - | - | - | On | - | - | 4 | 
| - | - | - | - | - | - | --- | 
| On | On | On | On | On | On | 63 | 
| - | - | - | - | - | - | EEPROM | 
c) Set the status of the RS-485 terminator.
| DIP Switch position 10 | Status | 
| -- | Disabled | 
| On | Enabled | 
- Set all SW2 DIP switches to ON to set all input ports to measure current.
 Avensor only supports the SENECA Z-8AI module when it is used as an input for a 4–20 mA current.
| DIP Switch position 1-8 | Mode | 
| -- | Voltage | 
| On | Current | 
- 
To configure the channels update the following registers with a Modbus tool. Make sure that the tool aligns with your security and operational requirements. Registers for electrical input Range: ±10000 [mV] for voltage, ±20000 [µA] for current Interpretation of register: Word Input Register Input 1 40014 40015 Input 2 40020 40021 Input 3 40026 40027 Input 4 40032 40033 Input 5 40038 40039 Input 6 40044 40045 Input 7 40050 40051 Input 8 40056 40057 Registers for the value to show or scale Range: ±32000 Interpretation of register: Word Input Register Input 1 40016 40017 Input 2 40023 40024 Input 3 40028 40029 Input 4 40034 40035 Input 5 40040 40041 Input 6 40046 40047 Input 7 40052 40053 Input 8 40058 40059 For further details on register values and setup, refer to the device documentation.