MAS 801 Configuration
The unit is connected to this device through the following terminals:
| CCD 401 | MAS 801 | 
| RS-485 A | Modbus A+ | 
| RS-485 B | Modbus B+ | 
- Go to Settings
- In the Modbus RTU group, set the following parameters:
| Parameter | Setting | 
| Enable | Enabled | 
| Baudrate | 19200 | 
| Parity | None | 
| Stop bits | 2 | 
- Click Save.
Note:
- One MAS 801 device must be added in Avensor for each pump.
- The Modbus ID in Avensor must correspond to the Modbus ID in the MAS 801 device.
- The Modbus id mapping group in the MAS 801 device shows the Modbus ID of each pump.