PS 200 Configuration

The PS 200 must have a RMBA-01 Modbus adapter module installed in slot 1 for Modbus communication over RS-485.

Set the following parameters in the PS 200 device:

Parameter Parameter name Setting
30.01 FIELDBUS STD MODBUS
30.03 COMM PROFILE CSA2.8/3.0
52.01 STATION NUMBER User defined
52.02 BAUD RATE 9600
52.03 PARITY NONE1STOPBIT