FPG 413 / FPG 414 / FPG 415-konfiguration

Brug FOP 315 eller FOP 402 HMI til at konfigurere FPG 413-, FPG 414- eller FPG 415-enheden.

  1. tilIndstillinger > Kommunikation.
  2. Vælg Modbus RTU eller Modbus TCP.
  3. Indstil kommunikationsparametrene.
ParameterIndstilling
StandardportIndstillingerne for kommunikation over Ethernet.
IP-adresse10.10.10.10
Subnetmaske255.0.0.0
SlaveadresseModbus-adressen i netværket.
Baud9600
Stopbits1
ParitetIngen
Port502

 

Et tab i feltbuskommunikation kan stoppe pumperne. Brug følgende indstillinger for at forhindre uventede pumpestop:

Indstillinger → Alarmer → Pumpe X → Feltbus kommunikationstab

Deaktiver Halt-pumpen.